Map Dictionary:
CMD0 - Specifies input and output locations for the command interface
DI - DeviceNet Input Table, as bits. DeviceNet tables are 125 words (16 bit) long.
DO - DeviceNet Output Table, as bits
DFI - DeviceNet Input, regarded as floats
DFO - DeviceNet Output, regarded as floats
DSI - DeviceNet Input, regarded as 16 bit integers
DSO - DeviceNet Output, regarded as 16 bit integers
DII - DeviceNet Input, regarded as 32 bit integers
DIO - DeviceNet Output, regarded as 32 bit integers
DTO - DeviceNet Output, regarded as text
DTI - DeviceNet Input, regarded as text
HI - Hardy Input Table (Boolean)
- HI0.0 - HI0.4 = digital input 1-5
- HI2.0-HI2.11 = Setpoint 1-12 output
- HI2.12-HI2.15 = Scale 1-4 in Motion
HSI - Hardy Input Table (Word)
- HSI1 = Instrument Status Word. See the bit definitions below
- HI1.0 = A/D error
- HI1.1 = A/D failure
- HI1.6 = Motion
- HI1.7 = Email Failure
- HI1.8 = NVR Failure
- HI1.9 = Infrared Failure
- HSI2 = Setpoint Output Word
- HSI3,HSI4,HSI5,HSI6 = Command Status Word, Chan 1,2,3,4. This 16-bit word holds the result status of mapped commands.
- HSI3.15, HSI4.15, HSI5.15,HSI6.15 = Command Status Data Valid. This bit is set when the rest of the status bits are valid.
- Status = 1,2,0x40 - calibration failed due to A/D error, A/D failure, or motion
- Status -8 (0xFFF8) = Hard Calibration failed, not enough ADC counts between high and low steps
- Status -6 (0xFFFA) = C2 Calibration failed, no C2 sensors detected
- Status -10 (0xFFF6) = C2 Calibration failed, bad C2 sensors detected
- HSI7 = Watchdog Word. Each bit represents the corresponding node(bit0=Node0 etc.) sending data. Five seconds after the last data packet arrives form any node, its bit is set to zero.
- HSI8,HSI9,HSI10,HSI11 - Status word for A/D channels 1-4
- HSIX.0 = A/D error
- HSIX.1 = A/D failure
- HSIX.6 = Motion
HO - Hardy Output Table
- HO0.0-HO0.6 = Output Relay 1-7
- HO0.7 = Software LED (on back of unit)
- HO1.0-HO1.3 = Tare Channel 1-4
- HO1.4-HO1.7 = Zero Channel 1-4
- HO1.12-HO1.15 = Print Channel 1-4
- HO2.0-HO2.3 = C2 Calibrate Chan 1-4
- HO2.4-HO2.7 = Trad Cal Low Ch 1-4
- HO2.8-HO2.11 = Trad Cal High Ch 1-4
- HO3.0-HO3.9 = Send Custom Email 0-9
HFI - Hardy Float Input Table
- HFI4-7 = gross weight on chan 1-4
- HFI8-11 = net weight on chan 1-4
- HFI12-15 = peak weight on chan 1-4
- HFI16-19 = Rate of Change on channels 1-4
HFO - Hardy Float Output Table
- HFO[ 0- 7] - 8 user defined floating point scratchpad variables, saved in non-volatile RAM
- HFO9-20 - Setpoint 1-12 input
- HFO21-24 - Tare Wt ch 1-4
- HFO25-28 - Motion Tolerance ch 1-4
- HFO29-32 - Zero Tolerance ch 1-4
- HFO33-36 - AutoZero Tolerance ch 1-4
- HFO37-40 - Capacity ch 1-4
- HFO41-44 - Cal Low Wt ch 1-4
- HFO45-48 - Span Wt ch 1-4
- HFO49-60 - Setpoint 1-12 Target Wt
- HFO61-72 - Setpoint 1-12 Preact Wt
- HFO73-84 - Setpoint 1-12 Deadband Wt
- HFO85-HFO88 - Analog Output Card, Slot 0
- HFO89-HFO92 - Analog Output Card, Slot 1
HSO - Hardy Short Output table. A table of 16 bit integers.
- HSO0 Setpoint and Motion Word
- HSO1-4 Unit of Measure Ch 1-4
- HSO5-8 Decimal Point Ch 1-4
- HSO9-12 Grad Size Ch 1-4
- HSO13-16 WaverSaver Ch 1-4
- HSO17-20 Averages Ch 1-4
- HSO21-24 Use Auto Zero Ch 1-4
- HSO25-28 Zero Reminder Ch 1-4
- HSO29-32 Tare Reminder Ch 1-4
- HSO33-36 Channel 1-4 On
- HSO37 AutoPrint On
- HSO38 IR Enabled
- HSO39 Printer Baud
- HSO40 Printer Parity
- HSO41 Printer Data Bits
- HSO42 DeviceNet Baud
- HSO43 DeviceNet Node
- HSO44 RIO Baud
- HSO45 RIO Address
- HSO46 RIO Rack Size
- HSO47 RIO Quarter
- HSO48 RIO Last Quarter
- HSO49 ControlNet Address
- HSO50 Profibus Node Number
- HSO51 Profibus Out Size
- HSO52 Profibus In Size
- HSO53 Setup Menu Security
- HSO54 Calibration Menu Security
- HSO55 Options Menu Security
- HSO56 Mapping Menu Security
- HSO57 Medium Level Password
- HSO58 High Level Password
- HSO59-62 Calibration Type Ch 1-4
- HSO67-70 Calibration Month Ch 1-4
- HSO71-74 Calibration Day Ch 1-4
- HSO75-78 Calibration Hour Ch 1-4
- HSO79-82 Calibration Minute Ch 1-4
- HSO83-86 Calibration Second Ch 1-4
HTO - Hardy Text Output table.
- HTO0 Operator ID
- HTO1 Instrument ID
- HTO2-HTO5 Channel 1-4 Name
- HTO6-HTO15 Custom Text 0-9
HTI - Hardy Text Input table.
- HTI0-HTI3 Calibrator ID Ch 1-4
- HTI4 Model Number
- HTI5 Program Part Number
- HTI6 Firmware Revision
HII - Hardy Integer Input table.
- HII0 IP Address
- HII1 IP Mask Address
- HII2 IP Gateway Address
- HII3 IP DNS Address
- HII4 Serial Number
EO, EFO, ESO, EIO, ETO- Hardy Control Link Output tables
- EO = Hardy Control Link output, addressed as bits
- EFO = Hardy Control Link output, addressed as floats
- ESO = Hardy Control Link output, addressed as 16 bit integers
- EIO = Hardy Control Link output, addressed as 32 bit integers
- ETO = Hardy Control Link output, addressed as text
0I, 0FI, 0SI, 0SO, 0II, 0IO, 0TI, 0TO- Hardy Control Link Input tables, from Node 0
- 0I = Hardy Control Link input from Node 0, addressed as bits
- 0FI = Hardy Control Link input from Node 0, addressed as floats
- 0SI = Hardy Control Link input from Node 0, addressed as 16 bit integers
- 0II = Hardy Control Link input from Node 0, addressed as 32 bit integers
- 0TI = Hardy Control Link input from Node 0, addressed as text
- 1I, 1FI, 1SI, 1SO, 1II, 1IO, 1TI, 1TO- Hardy Control Link Input tables, from Node 1
- 2I, 2FI, 2SI, 2SO, 2II, 2IO, 2TI, 2TO- Hardy Control Link Input tables, from Node 2
- ...
- 9I, 9FI, 9SI, 9SO, 9II, 9IO, 9TI, 9TO- Hardy Control Link Input tables, from Node 9
- UI, UFI, USI, USO, UII, UIO, UTI, UTO- Hardy Control Link Input tables, from Node 10
- VI, VFI, VSI, VSO, VII, VIO, VTI, VTO- Hardy Control Link Input tables, from Node 11
- ...
- ZI, ZFI, ZSI, ZSO, ZII, ZIO, ZTI, ZTO- Hardy Control Link Input tables, from Node 15
RI, RO, RFI, RFO, RSI, RSO, RII, RIO, RTI, RTO - RIO tables (used if you have an RIO option card)
- RI, RO = RIO input/output, addressed as bits
- RFI, RFO = RIO input/output, addressed as floats
- RSI, RSO = RIO input/output, addressed as 16 bit integers
- RII, RIO = RIO input/output, addressed as 32 bit integers
- RTI, RTO = RIO input/output, addressed as text
CI, CO, CFI, CFO, CSI, CSO, CII, CIO, CTI, CTO - Communications Network tables (used if you have a ControlNet, EtherNet/IP or Profibus option card)
- CI, CO = Communication Network input/output, addressed as bits
- CFI, CFO = Communication Network input/output, addressed as floats
- CSI, CSO = Communication Network input/output, addressed as 16 bit integers
- CII, CIO = Communication Network input/output, addressed as 32 bit integers
- CTI, CTO = Communication Network input/output, addressed as text
MI, MO, MFI, MFO, MSI, MSO, MII, MIO, MTI, MTO - Modbus tables (used if you have Modbus)
- MI, MO = Modbus input/output, addressed as bits
- MFI, MFO = Modbus input/output, addressed as floats
- MSI, MSO = Modbus input/output, addressed as 16 bit integers
- MII, MIO = Modbus input/output, addressed as 32 bit integers
- MTI, MTO = Modbus input/output, addressed as text
HVO The members in this table are displayed in the configured units (lb, kg, oz, g)
- HVO0-3 = Zero Tolerance, channels 1-4
- HVO4-7 = Motion Tolerance, channels 1-4
- HVO8-11 = Auto Zero Tolerance, channels 1-4
- HVO12-15 = Scale Capacity, channels 1-4
- HVO16-19 = Calibration reference weight, channels 1-4
- HVO20-23 = calibration span weight, channels 1-4
- HVO24-27 = peak weight, channels 1-4
- HVO28-31 = tare weight, channels 1-4